Forcing outside temperature to be at worst 0.1 K below the inside temperature (models.py)
This commit is contained in:
parent
a233a97334
commit
ff6f61e9c1
1 changed files with 7 additions and 1 deletions
|
|
@ -203,6 +203,9 @@ class WindowOpening(Ventilation):
|
|||
#: used to exchange air (0 <= cd_b <= 1)
|
||||
cd_b: float = 0.6
|
||||
|
||||
#: Minimum difference between inside and outside temperature
|
||||
min_deltaT: float = 0.1
|
||||
|
||||
def transition_times(self) -> typing.Set[float]:
|
||||
transitions = super().transition_times()
|
||||
transitions.update(self.inside_temp.transition_times)
|
||||
|
|
@ -218,7 +221,10 @@ class WindowOpening(Ventilation):
|
|||
outside_temp = self.outside_temp.value(time)
|
||||
|
||||
# Reminder, no dependence on time in the resulting calculation.
|
||||
temp_delta = abs(inside_temp - outside_temp) / outside_temp
|
||||
if outside_temp < (inside_temp-self.min_deltaT):
|
||||
temp_delta = (inside_temp - outside_temp) / outside_temp
|
||||
else:
|
||||
temp_delta = self.min_deltaT / outside_temp
|
||||
root = np.sqrt(9.81 * self.window_height * temp_delta)
|
||||
window_area = self.window_height * self.opening_length * self.number_of_windows
|
||||
return (3600 / (3 * room.volume)) * self.cd_b * window_area * root
|
||||
|
|
|
|||